研华ADAM-4080配置为Modbus-RTU

2022-06-13 18:24:44 浏览数 (1)

ADAM-4080 模块为 32 位计数和测频模块, 初始化的界面如下

通讯参数设置: 断电短接INIT和GND端子 通过软件设置为 Modbus 通讯方式 拆掉短接线,上电重启。

  • 测试结果
  • 通讯地址

ADDR 0X

Channel

Item

Attribute

Memo

00017

0

DO0 Signal/Counter 0Alarm Status

R/W

Alarm is read only

00018

1

DO1 Signal/Counter1Alarm Status

R/W

Alarm is read only

00033

Counter0 Start/Stop

R/W

1: start0: stop

00034

Counter0 Clear

W

1: clear counter

00035

Counter0 Overflow

R

00037

Counter1 Start/Stop

R/W

1: start0: stop

00038

Counter1 Clear

W

1: clear counter

00039

Counter1 Overflow

R

ADDR 4X

Channel

Item

Attribute

Memo

40001-40002

0

Counter 0 Value

R

40003-40004

1

Counter 1 Value

R

40201

Counter Mode

R

50:Counter51:Frequency

40202

Signal Input Mode

R

0: non-isolated (TTL)input 1:photo-isolated input

40203

Gate Mode

R

0:the gate is low1:the gate is high2:the gate is disabled

40204

Gate Time

R

0:0.1(s)1:1(s)

40205

0

Counter 0 Alarm output

R

1: Enable0: Disable

40206

1

Counter 1 Alarm output

R

1: Enable0: Disable

40211

Module Name 1

R

40213

Versoin 1

R

ADAM-4080 模块支持隔离和非隔离输入方式, 在非隔离输入情况下,支持可编程的阈值。模块可以通过门控信号触发计数器开始计数,有可编程数字滤波的功能。 非隔离信号:逻辑 0=0~5V(默认 0.8V)可编程 逻辑 1=0~5V(默认 2.4V)可编程 隔离信号:逻辑 0=1V(最大) 逻辑 1=3.5~30V

0 人点赞